stranded copper conductor - conductor screen of semiconducting compound - XLPE insulation - core screen of semiconducting compound - copper tape screen - separation tape - PVC sheath
suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground as well as for installation on cable trays for industries, switchboards and power stations.
STANDERInternational:IEC60502-2 National:GB/T 12706.1-2008 |
CONSTRUCTION:1. CONDUCTOR – Bare copper class 2 to IEC 60228, round, multiwire stranded and compact 2. CONDUCTOR SCREEN – Inner semi-conducting coating 3. INSULATION – Core insulation of cross-linked polyethylene (XLPE) 4. INSULATION SCREEN – Outer conductive layer extruded and per-manently welded with the core insulation Semi-conducting type 5. METAL SCREEN – copper tapes helically with a minimum thickness of 0,1 mm. Separator 6. SHEATH – Outer sheath of PVC compound |
Construction characteristics |
|
Conductor shape | Circular stranded (RM) |
Lead free | Yes |
Insulation | XLPE |
Screen | copper tape |
Material of bedding | Separation tape |
Outer sheath | PVC |
DIMENSIONAL CHARACTERISTICS | |
Number of cores | 1& 3 core |
ELECTRICAL CHARACTERISTICS | |
Nominal Voltage Uo/U | 3,6 / 6 kV |
Operating Voltage (Um) | 7,2 kV |
Testing Voltage | 12.5 kV (5 Min) |
Usage characteristics | |
Packaging | Steel Wooden Drum |
Minimum installation temperature | -20 °C |
Max. conductor temperature in service | 90 °C |
Short-circuit max. conductor temperature | 250 °C |
Bending factor when laying |
20 x D single core cable 15 x D multi-core cable |
nominal cross section | Operation voltage max. |
Nominal voltage U0/U |
Insulation thickness |
Sheath thickness Nominal value |
Outer Ø approx. |
weight approx. |
Current ratings in air 30℃ | Current ratings buried 20℃ | maximum DC resistance at 20℃ |
---|---|---|---|---|---|---|---|---|---|
mm² | kV | kV | mm | mm | mm | kg / km | A | A | Ω/km |
35 | 7.2 | 3.6 / 6 | 2.5 | 1.6 | 18.4 | 616 | 205 | 190 | 0.52 |
50 | 7.2 | 3.6 / 6 | 2.5 | 1.7 | 19.9 | 788 | 245 | 225 | 0.39 |
70 | 7.2 | 3.6 / 6 | 2.5 | 1.7 | 21 | 999 | 305 | 275 | 0.27 |
95 | 7.2 | 3.6 / 6 | 2.5 | 1.8 | 23.5 | 1276 | 370 | 330 | 0.19 |
120 | 7.2 | 3.6 / 6 | 2.5 | 1.8 | 24.9 | 1532 | 430 | 375 | 0.15 |
150 | 7.2 | 3.6 / 6 | 2.5 | 1.9 | 26.7 | 1849 | 490 | 425 | 0.12 |
185 | 7.2 | 3.6 / 6 | 2.5 | 1.9 | 28.3 | 2197 | 560 | 480 | 0.10 |
240 | 7.2 | 3.6 / 6 | 2.6 | 2.0 | 30.7 | 2763 | 665 | 555 | 0.08 |
300 | 7.2 | 3.6 / 6 | 2.8 | 2.1 | 33.7 | 3391 | 765 | 630 | 0.06 |
400 | 7.2 | 3.6 / 6 | 3.0 | 2.2 | 38.9 | 4433 | 890 | 725 | 0.05 |
500 | 7.2 | 3.6 / 6 | 3.2 | 2.3 | 42.2 | 5474 | 1030 | 825 | 0.04 |
630 | 7.2 | 3.6 / 6 | 3.2 | 2.4 | 45.6 | 6751 | 1190 | 940 | 0.03 |
No. of cores | nominal cross section | Operation voltage max. |
Nominal voltage U0/U |
Insulation thickness |
Sheath thickness Nominal value |
Outer Ø approx. |
weight approx. |
Current ratings in air 30℃ | Current ratings buried 20℃ | maximum DC resistance at 20℃ |
---|---|---|---|---|---|---|---|---|---|---|
No. | mm² | kV | kV | mm | mm | mm | kg / km | A | A | Ω/km |
3 | 35 | 7.2 | 3.6 / 6 | 2.5 | 2.2 | 38.5 | 2073 | 142 | 185 | 0.52 |
3 | 50 | 7.2 | 3.6 / 6 | 2.5 | 2.3 | 41.5 | 2614 | 169 | 216 | 0.39 |
3 | 70 | 7.2 | 3.6 / 6 | 2.5 | 2.4 | 44.3 | 3317 | 210 | 264 | 0.27 |
3 | 95 | 7.2 | 3.6 / 6 | 2.5 | 2.5 | 49.3 | 4183 | 257 | 316 | 0.19 |
3 | 120 | 7.2 | 3.6 / 6 | 2.5 | 2.6 | 52.5 | 5014 | 298 | 360 | 0.15 |
3 | 150 | 7.2 | 3.6 / 6 | 2.5 | 2.7 | 56.1 | 6000 | 336 | 402 | 0.12 |
3 | 185 | 7.2 | 3.6 / 6 | 2.5 | 2.8 | 59.8 | 7154 | 393 | 461 | 0.10 |
3 | 240 | 7.2 | 3.6 / 6 | 2.6 | 3.0 | 64.9 | 8925 | 463 | 533 | 0.08 |
3 | 300 | 7.2 | 3.6 / 6 | 2.8 | 3.2 | 71.3 | 10937 | 526 | 599 | 0.06 |
3 | 400 | 7.2 | 3.6 / 6 | 3.0 | 3.5 | 80.3 | 14214 | 605 | 680 | 0.05 |
*Dimensions and specifications may be changed without prior notice.
MEDIUM VOLTAGE CABLE TESTING
Routine tests: | Sample tests: | Type tests: |
These non-destructive tests are normally carried out on all lengths manufactured. - Conductor resistivity - Spark test on oversheath - Voltage tests on sheath - D.C. voltage test on oversheath |
These potentially destructive tests are normally carried out on every production run. - Examination of conductor and dimensions - Hot set test for XLPE insulation - Insulation and oversheath thickness - Four hour voltage test |
These destructive tests are normally carried out in addition to the above tests on commencement of a particular cable supply to validate its design. - Electrical type tests including bending and heat cycle - Non-electrical type tests including mechanical properties after ageing and tests under fire conditions. |
PACKING AND SHIPPING
Packing: steel wooden drum, other as required ; standard delivery length is 300 m
Packaging details : |
Delivery : |
|
Steel Wooden Drums | Cable Drum In container | shipped in 15 days after payment |
CABLE DRUMS | D1=Flange Diameter(mm) | W=Useful Width (mm) | D2=Barrel Diameter(mm) |
1000 | 700 | 500 | |
1100 | 700 | 550 | |
1200 | 700 | 600 | |
1400 | 750 | 710 | |
1600 | 900 | 900 | |
1800 | 1120 | 1000 | |
2400 | 1150 | 1300 |
Delivery Port:
Port of Shenzhen | Port of Hongkong | Port of Guangzhou |
Our production in numbers
● Cable production started 1983 ● Sales in 2016 about 500 million USD ● 100,000 m2 Production area |
● 200 Sets Of Testing Equipment ● 100 Testing Items |
Certificat | Information | |
ISO 9001:2008
Quality management systems
|
Certificat ISO 9001:2008 - Shenzhen chengtiantai cable industry development Co.Ltd. ; Certified through Guangdong quality Testing CTC Certification Co.Ltd.; Valid until 9th January 2022 |
|
ISO 14001:2004
Environmental management systems
|
Certificat ISO 14001:2004 - Shenzhen chengtiantai cable industry development Co.Ltd. ; Certified through Guangdong quality Testing CTC Certification Co.Ltd.; Valid until 9th January 2022 |
|
OHSAS 18001:2007
Assessment specification for occupational health & safety management systemsenvironmental management systems
|
Certificat OHSAS 18001:2007 - Shenzhen chengtiantai cable industry development Co.Ltd. ; Certified through Guangdong quality Testing CTC Certification Co.Ltd.; Valid until 9th January 2022 |
1. copper rod | 2. wire drawing | 3. wire stranding |
4.Triple Extrusion Insulation | 5.Screening Process | 6. outer covering Process |
7. Sheath Marking | 8. Packing | 9. Partial discharge Inspection |
RECOMMENDED ORDERING PARAMETERS |
CONTACT |
For prompt quotation / supplies please make sure your inquiries and your orders are 1 - International or Special Standard. (Alternatively, the precise usage of the cable.) |
If this all seems a litle too technical for you, then why not get in touch with us.
We look forward to assisting you in identifying the best products for your specific application and to answer any questions you might have.
Tel:+86 755 6114 5028 |
For a period commencing on the date shipped the Goods to Buyer and continuing for a period of 12 months thereafter.